SOP on Operation of Air Handling Unit

Rahul Kashyap
4
Purpose
To describe the procedure for operation of AHU.
Pre Requisite:
  • Check the cleanliness of AHU it should be clean.
  • Check Power supply.
  • Ensure that there should not be any leakage in AHU Doors/Frame.
  • Ensure that supply air damper, return air damper, fresh air damper and bleed air
  • damper is in open position on the marked position, Frequency for damper position verification to is weekly and should be verified by QA Personnel record damper position.
  • Ensure that hot water generator is working
  • Check & ensure that silicon tube of Differential pressure switch is mounted across filters to monitor differential pressure should be properly fitted at their places.
  • Starting Procedure:
  • Switch ON the main supply from the main HVAC panel a red indicator will glow up.
  • Switch ON MCB’s mounted inside the AHU control panel RYB indication glow on AHU control panel.
  • Switch ON the AHU blowers by turning selector switch to on position from control Panel.
  • To Switch ON outdoor unit set selector switch to Auto mode.
  • Set the required temperature & RH on Temperature & RH Controller.        
  • Observe for any abnormality in running of AHU, if found rectify it.
  • Check the pressure of Hot water. It should be NLT 1.5 kg/cm2.
  • Differential pressure across the filter shall be as follow:
  • Differential pressure across pre filter shall be NMT 160Pa. In case of increase of DP.
  • Indication will glow on the panel for cleaning of filter, take the filter for cleaning
  • Differential pressure across fine filter shall be NMT 180Pa. In case of increase of DP, Indication will glow on the panel for cleaning of filter, take the filter for cleaning.
  • Frequency of monitoring of Temperature & RH & Differential Pressure is twice in a day
Shut down Procedure:
  • Switch OFF the AHU blower by turning selector switch to off position from control
  • panel Also switch off outdoor unit set selector switch to zero mode.
  • Switch off MCB’s mounted inside the AHU control panel.
  • Switch OFF the main supply of the operating panel of AHU by turning selector switch to off position.


Post a Comment

4Comments
  1. You are providing good knowledge. It is really helpful and factual information for us and everyone to increase knowledge about air duct cleaning chicago. Continue sharing your data. Thank you.

    ReplyDelete
  2. This is excellent information which is shared by you. This information is meaningful and magnificent for us to increase our knowledge aboutair duct cleaning in chicago . Keep sharing this kind of information. Thank you.

    ReplyDelete
  3. I always check this type of advisory post and I found your article which is related to my interest.Air Cooler For Sale Online Pakistan This is a great way to increase knowledge for us. Thanks for sharing an article like this.

    ReplyDelete
  4. reading the SOP of pharma, or CGMP plant, does not give any information., there sop meant to be shown to the auditor.
    i have not seen any safety related check list during the preventive maintenance.
    of equipment
    DQ IQ,OQ not contained any technical information or specification. of components. all this nonsense

    ReplyDelete
Post a Comment